  • What is being procured: Replacement of the uninterruptible power supply (UPS) battery packs for the Enefit 280 turbine hall.
  • Main technical requirements, features:
    • 80 existing battery cells are to be replaced with new Sprinter XP12V3000 type or equivalents.
    • Required parameters for equivalents: Voltage 12 VDC, Capacity 92.8 Ah, Technology AGM, Terminal type M6 bolt connection.
    • The scope of work includes the dismantling and disposal of old cells…
       