Replacement of Eaton IZM40N3-V40W air circuit breaker AI

TEDAS your procurement assistant

Ask a question about this procurement

t

Procurement Object

  • What is being procured: Replacement of Eaton IZM40N3-V40W air circuit breaker.
  • Main technical requirements, features:
    • Circuit breaker type: Air circuit breaker.
    • Installation method: Draw-out type for basket/cassette installation.
    • Rated frame current ($I_n$): 4000 A.
    • Number of poles: 3.
    • Compliance with standards: IEC/EN 60947-2.
    • Rated voltage ($U_e$): 440 V / 690 V.
    • Rated short-circuit breaking capacity ($I_{cu}$): At least 85 kA @ 440 V;…
       